USA / SERVER CPU / AMD EPYC + INTEL XEON — RFQ COORDINATION

Server CPU Liquid Cold Plates for US Data Centers

Direct Answer:

ToneCooling Texas supports US data-center and server-OEM teams with direct-to-chip CPU liquid cold plate RFQs for AMD EPYC (SP5) and Intel Xeon (Birch Stream) platforms — with US-hours DFM review and prototype coordination.

RFQ inputs for faster DFM review:
  • 2D or 3D drawings
  • Heat load and heat-source map
  • Coolant, flow rate, and pressure-drop limit
  • Envelope, mounting, and port layout
  • Material and joining preference
  • Prototype quantity and annual volume

ToneCooling Texas LLC coordinates US RFQs for custom server-CPU direct-to-chip cold plates built in purple copper (Cu T2). US-hours DFM review, engineer-reviewed RFQs, and production through our 30,000 m² ISO 9001:2015-certified, IATF 16949-aligned facility in Huizhou, China.

Engineer-reviewed RFQs (Central Time)US-hours engineering & DFM reviewISO 9001:2015 certified · IATF 16949-alignedAMD EPYC & Intel Xeon experience
ENGINEERING SCOPE

Direct-to-chip CPU cold plates for US server programs

ToneCooling Texas supports US server OEMs, system integrators, and data-center operators with custom direct-to-chip liquid cold plates for AMD EPYC (SP5) and Intel Xeon (Birch Stream) CPUs. Each plate is engineered to your socket and drawing, CFD-validated, and 100% helium leak-tested.

REFERENCE COLD PLATES

Validated server-CPU cold plates (reference specs)

AMD EPYC SP5 CPU cold plate

AMD EPYC SP5 CPU liquid cold plate in purple copper with hoses and quick disconnects, supplied by ToneCooling Texas LLC
Heat dissipation (design-rated)550 W × 2
MaterialPurple copper (Cu T2)
JoiningConfirmed at quotation (DFM review)
Working point42 °C, 1 L/min, 25% EGW
Flow resistanceless than 3 kPa
Cold-plate surface tempbelow 52 °C
Pressure0.6 MPa
Dimensions118 × 92.4 × 25 mm

Intel Xeon (Birch Stream) CPU cold plate

Intel Xeon Birch Stream CPU liquid cold plate in purple copper with dual hoses and quick disconnects, supplied by ToneCooling Texas LLC
Heat dissipation (design-rated)500 W
MaterialPurple copper (Cu T2)
JoiningConfirmed at quotation (DFM review)
Working point40 °C, 1 LPM, 25% EGW
Flow resistance5 kPa
Cold-plate surface temp60 °C
Pressure1 MPa
Dimensions130 × 90 × 25 mm

Specifications are typical validated values at the stated working point; final values are confirmed per drawing, heat load, flow rate, pressure-drop limit, and annual volume.

MANUFACTURING ROUTE

Process, quality, and manufacturing disclosure

Process optionsFSW, vacuum brazing, CAB, and TLP diffusion bonding in copper (C1100) and aluminium (6061); CFD flow/thermal validation; 100% helium leak testing.
QualityISO 9001:2015 certified; IATF 16949-aligned quality system; 100% helium leak testing; thermal resistance, leak, and flatness test reports available.
US support roleToneCooling Texas handles RFQ intake, US-hours communication, NDA coordination, DFM follow-up, and US-side commercial routing for server-CPU cold plate programs. The Texas entity is a registered U.S. company (Austin, TX), not a manufacturing site.
Manufacturing disclosureManufacturing is performed by ToneCooling Technology Co., Ltd at the 30,000 m² facility in Huizhou, Guangdong, China (since 2004). ToneCooling Texas LLC is the North American RFQ and engineering-communication entity and does not manufacture.

Ready to discuss your liquid cooling project?

An engineer reviews every RFQ and replies by email with next steps. Send drawings, specs, or a project description.

FREQUENTLY ASKED

Common questions from US engineering & procurement teams

Do you make liquid cold plates for server CPUs?

Yes. ToneCooling Texas coordinates US RFQs for custom direct-to-chip CPU cold plates for AMD EPYC (SP5) and Intel Xeon (Birch Stream) platforms, engineered to your drawing.

Which CPU platforms do you support?

AMD EPYC SP5 and Intel Xeon (Birch Stream) are common; other sockets are supported per your drawing and mounting interface.

What joining process is used for CPU cold plates?

Purple copper (Cu T2); the joining process is selected at DFM review and confirmed at quotation, with CFD validation and 100% helium leak testing.

What is the lead time?

Prototype lead time is typically 4–6 weeks after drawing approval; production timing depends on volume and is confirmed per RFQ.