Dry Cooler vs Cooling Tower for Data Centers

A cooling tower cools water toward the wet-bulb temperature by evaporating water; a dry cooler cools toward the dry-bulb temperature with zero evaporative water. For warm-water liquid cooling, a dry cooler such as the TC-DC1000 (1000 kW class at 104 °F ambient) removes about 36 m³ (9,500 US gal) of evaporation per MW per day from the site's water demand.

How do they compare?

Cooling towerDry cooler
Heat rejectionEvaporation (latent) plus some sensibleSensible only, through a finned coil
Cools towardOutdoor wet-bulbOutdoor dry-bulb
Water useContinuous makeup for evaporation, blowdown and driftNone for heat rejection
Water treatmentRequired (scale, corrosion, biological control)Closed glycol loop only
Best loop temperatureLow to medium (chilled-water plants)Warm (direct-to-chip liquid cooling)
Site riskWater permits, plume, Legionella managementHot-day capacity: check rating at design dry-bulb

How much water does a cooling tower evaporate?

Evaporating water absorbs about 2,400 kJ/kg. One kWh is 3,600 kJ, so rejecting 1 kWh of heat by evaporation consumes about 1.5 L of water. A steady 1 MW load therefore evaporates about 1,500 L per hour, or about 36 m³ per day, before blowdown and drift are added.

Cooling tower, 1 MW≈ 36 m³/day evaporated (≈ 9,500 US gal) Dry cooler, 1 MW0 m³/day evaporative water
Evaporation only, steady 1 MW load, all heat rejected by evaporation. Blowdown and drift add to the tower figure.

When does a dry cooler win?

Direct-to-chip cold plates return warm water, so the facility loop can often run at 40 °C (104 °F) or higher. A dry cooler can hold that supply on most US days and avoids water permits, chemical treatment and plume. The trade-off is the hottest hours: a dry cooler cannot cool below dry-bulb, so check its rating at your site's summer design condition.

What glycol temperature can TC-DC1000 hold at other ambient temperatures?

At the rated flows, fan speed and a 1000 kW load, the leaving glycol stays about 9 K above outdoor air. Use this table to check the supply temperature you can deliver to the CDU in your climate:

Ambient airGlycol in → out at 1000 kWApproach
10 °C (50 °F)25 → 19 °C (77 → 66 °F)9 K (16 °F)
15 °C (59 °F)30 → 24 °C (86 → 75 °F)9 K (16 °F)
20 °C (68 °F)35 → 29 °C (95 → 84 °F)9 K (16 °F)
25 °C (77 °F)40 → 34 °C (104 → 93 °F)9 K (16 °F)
30 °C (86 °F)45 → 39 °C (113 → 102 °F)9 K (16 °F)
35 °C (95 °F)50 → 44 °C (122 → 111 °F)9 K (16 °F)
40 °C (104 °F)55 → 49 °C (131 → 120 °F)9 K (16 °F)

Calculated from the rated point (40 °C air, 55/49 °C, 162 m³/h, 300,000 m³/h) assuming constant heat-exchanger effectiveness, flows and fluid properties. These are calculated values, not test data; the final selection is confirmed at quotation.

When is a cooling tower still the right tool?

If the loop must run near or below outdoor dry-bulb, as in chilled-water plants, use a cooling tower or chiller. Many sites combine both: dry coolers for the warm liquid-cooling loop and a smaller chilled-water plant for air-cooled IT.

Related: coolant distribution units · data center liquid cooling in the USA

Frequently asked questions

What is the difference between a dry cooler and a cooling tower?

A cooling tower rejects heat mainly by evaporating water, so it can cool water close to the outdoor wet-bulb temperature but consumes water continuously. A dry cooler rejects heat sensibly through a finned coil, uses no evaporative water, and cools the loop to a few degrees above the dry-bulb temperature.

How much water does a cooling tower use per MW?

Evaporating water absorbs about 2,400 kJ/kg, so rejecting 1 kWh of heat by evaporation consumes about 1.5 L of water. At a steady 1 MW that is roughly 1,500 L (about 400 US gal) per hour, or about 36 m³ per day, before blowdown and drift.

When is a dry cooler the better choice for a data center?

When the liquid-cooling loop runs warm (for example 40 °C supply or higher), when water supply or discharge permits are limited, or when the operator wants to avoid water treatment. Hot-climate sites should check the dry cooler rating at their design dry-bulb.

When is a cooling tower still better?

When the loop must run close to or below the outdoor dry-bulb temperature, for example for chilled-water systems, a cooling tower or a chiller is needed because a dry cooler cannot cool below ambient dry-bulb.

What does TC-DC1000 deliver in a US summer?

TC-DC1000 is rated at 1000 kW class with 104 °F (40 °C) ambient air, cooling 30 % ethylene glycol from 131 °F to 120 °F (55 °C to 49 °C) with no evaporative water.

Compare options for your site

Send the heat load, location and loop temperatures. An engineer reviews every RFQ and replies by email with next steps.