USA · Data center heat rejection

Data Center Dry Cooler for US Liquid-Cooled Sites: TC-DC1000, 1000 kW

A data center dry cooler rejects CDU heat to outdoor air with zero evaporative water use. TC-DC1000 is a 1000 kW class V-type unit rated at 40 °C (104 °F) ambient: it cools 162 m³/h (about 713 US gpm) of 30 % ethylene glycol from 55 °C to 49 °C (131 °F to 120 °F) with 10 Ø910 mm fans and built-in circulation pumps.

ToneCooling Texas LLC coordinates US RFQs, documents and delivery for this standard model; options are customized per project.

English PDF · free download · no form required

Data center dry cooler TC-DC1000, 1000 kW V-type unit with ten fans
TC-DC1000 V-type dry cooler: 10 axial fans over two plate-fin V-coils.
1000 kWclass, 2 × ≥ 500 kW
40 °Cdesign ambient
55 → 49 °CEG30 loop
162 m³/hliquid flow
10 × Ø910axial fans
4.7 moverall length

Why US operators are moving heat rejection to dry coolers

Direct-to-chip liquid cooling returns warm water, so the facility loop can run hot enough to reject heat to air for most or all of the year. That removes cooling-tower makeup water, blowdown and chemical treatment from the site, which is increasingly important where water permits shape where a data center can be built.

The trade-off is climate. A dry cooler can only cool the loop to a few degrees above outdoor dry-bulb, so the rating point matters more than the nameplate. TC-DC1000 is rated at 40 °C (104 °F) with a 49 °C (120 °F) leaving temperature, a 9 K approach that covers most US summer design conditions for warm-water loops. Where your design dry-bulb is higher, as in parts of the desert Southwest, ask for a selection at your actual point.

TC-DC1000 3D model with V-coils, fans and circulation pumps
Circulation pumps and controls sit at the header end of the frame.

TC-DC1000 specifications

ParameterValue
ConfigurationV-shaped coil, 2 coil halves, circulation pumps included
Heat exchanger typeAluminum plate-fin, cross flow
Heat rejection2 × ≥ 500 kW per coil half (incl. 20 % margin), 1000 kW class
Design ambient range−10 °C to 40 °C
Coolant / outside mediumEG30 (30 % ethylene glycol) / air
Passes (inside / outside)2 / 1
Coil half size (W × H × D)4500 × 2450 × 113 mm
Exchange area per coil half294 m² liquid side · 672 m² air side
Liquid inlet / outlet55 °C / 49 °C
Air inlet / outlet40 °C / 49.9 °C
Liquid flow162 m³/h
Air flow300,000 m³/h
Pressure drop, liquid / air1.1 bar / 65 Pa
Fans10 × Ø910 mm axial, 35,000 m³/h each (±10 %), 1160 r/min
Static pressure250 Pa
Total fan power33 kW
Power supply415 V / 3Ph / N / PE reference; voltage and frequency configured per project
Fan operating temperature−40 °C to 70 °C
Fan certificationUL
Overall length / height4700 mm / 2550 mm (frame 2236 mm)
Unit massapprox. 3,900 kg (2 × 1,950 kg)
FinishRAL 7035 light grey, coating thickness > 80 µm

US customary reference: 162 m³/h ≈ 713 US gpm; 300,000 m³/h ≈ 176,600 cfm; 4700 mm ≈ 15.4 ft; 3,900 kg ≈ 8,600 lb.

What glycol temperature can TC-DC1000 hold at other ambient temperatures?

At the rated flows, fan speed and a 1000 kW load, the leaving glycol stays about 9 K above outdoor air. Use this table to check the supply temperature you can deliver to the CDU in your climate:

Ambient airGlycol in → out at 1000 kWApproach
10 °C (50 °F)25 → 19 °C (77 → 66 °F)9 K (16 °F)
15 °C (59 °F)30 → 24 °C (86 → 75 °F)9 K (16 °F)
20 °C (68 °F)35 → 29 °C (95 → 84 °F)9 K (16 °F)
25 °C (77 °F)40 → 34 °C (104 → 93 °F)9 K (16 °F)
30 °C (86 °F)45 → 39 °C (113 → 102 °F)9 K (16 °F)
35 °C (95 °F)50 → 44 °C (122 → 111 °F)9 K (16 °F)
40 °C (104 °F)55 → 49 °C (131 → 120 °F)9 K (16 °F)

Calculated from the rated point (40 °C air, 55/49 °C, 162 m³/h, 300,000 m³/h) assuming constant heat-exchanger effectiveness, flows and fluid properties. These are calculated values, not test data; the final selection is confirmed at quotation.

Selection points for a US site

Design condition

Use your site's summer design dry-bulb, not the monthly average. Rated duty is stated at 40 °C ambient; other points are calculated at quotation.

Loop temperature

The 55 / 49 °C EG30 rating suits warm-water cold plate loops. Check the leaving temperature against the CDU and IT inlet limit with your integrator.

Power and listing

The reference supply is 415 V / 60 Hz / 3Ph. State the US voltage, frequency and required listings in the RFQ so they are configured and confirmed per project.

General arrangement

TC-DC1000 data center dry cooler general arrangement, 4700 mm long and 2550 mm high
Outline dimensions in mm. Width, connections and lifting points are confirmed on the project drawing.

What to include in a US RFQ

  • Heat load (kW or tons) and required leaving liquid temperature
  • Site location and summer design dry-bulb
  • Coolant type and concentration
  • Supply voltage, frequency and phases
  • Sound limits at the property line, if any
  • Plot plan with clearances and delivery access

Related: dry cooler vs cooling tower · coolant distribution units for US data centers · data center liquid cooling in the USA · GB300 cold plates

Frequently asked questions

What does a dry cooler do in a liquid-cooled data center?

A dry cooler rejects the heat collected by direct-to-chip cold plates and the CDU to outdoor air through a finned coil and fans. It is a closed loop, so there is no evaporative water use and no water treatment, which matters where water rights or makeup water are limited.

Can TC-DC1000 work in a US summer?

TC-DC1000 is rated at 40 °C (104 °F) ambient, rejecting 1000 kW class duty from a 55 °C to 49 °C glycol loop. Where a site design dry-bulb is above 40 °C, we run a selection at your actual design point before quoting.

Is it available for 60 Hz power?

The specification reference is 415 V / 60 Hz / 3Ph / N / PE. Supply voltage and frequency for a US site (for example 460–480 V, 60 Hz) are configured per project and confirmed at quotation.

Are the fans UL certified?

The TC-DC1000 datasheet lists UL certification for the fans; this is a fan component listing, not a listing of the complete unit. Overall unit listing requirements for your jurisdiction should be stated in the RFQ so they can be confirmed at quotation.

Is TC-DC1000 standard or custom?

It is a standard model supplied by ToneCooling from China to its datasheet; coil, fan, power and control options can be customized for a project. ToneCooling Texas LLC (Austin, TX) handles US RFQs and does not manufacture. Lead time is confirmed at quotation.

How does ToneCooling Texas handle US RFQs?

ToneCooling Texas LLC coordinates US quotations, documentation and logistics. Send the heat load, design ambient, loop temperatures and power supply; an engineer reviews every RFQ and replies by email with next steps.

Request a TC-DC1000 quote in the USA

Send your heat load, design ambient, loop temperatures and power supply. An engineer reviews every RFQ and replies by email with next steps.