USA / AI SERVER COOLING — RFQ COORDINATION

Custom GPU Server Cold Plates for US AI Data Centers

Direct Answer:

ToneCooling is a custom cold plate manufacturer for GPU servers in the USA market: cold plates are made in our own manufacturing facility in Huizhou, and US RFQs are handled by ToneCooling Texas LLC in Austin, TX. A custom GPU server cold plate is a direct-to-chip liquid cold plate built to a specific GPU or CPU tray layout, heat load, and coolant loop. ToneCooling supplies standard kits for NVIDIA GB300 (4 GPU + 2 CPU), GB200, H200, and H100 according to their spec sheets, and custom cold plates for other GPU, CPU, and accelerator layouts after a DFM review.

RFQ inputs for faster DFM review:
  • 2D or 3D drawings
  • Heat load and heat-source map
  • Coolant, flow rate, and pressure-drop limit
  • Envelope, mounting, and port layout
  • Material and joining preference
  • Prototype quantity and annual volume

ToneCooling Texas LLC coordinates US RFQs for AI-server direct-to-chip cooling. Cold plates are made in our own manufacturing facility in Huizhou (ISO 9001:2015 certified, IATF 16949-aligned); manifolds, quick disconnects, and hose sets are supplied by ToneCooling from China. Custom samples are available from a single piece.

Engineer-reviewed RFQs (Central Time)US-hours engineering & DFM reviewISO 9001:2015 certified · IATF 16949-alignedDirect-to-chip & power-electronics experience
APPLICATION SCOPE

Direct-to-chip cooling for US AI servers and data centers

ToneCooling Texas supports US hyperscale, colocation, and AI-server OEM teams with direct-to-chip liquid cold plates and integrated GPU+CPU assemblies. We handle US-hours RFQ coordination, NDA, and DFM follow-up; engineering review runs through ToneCooling's thermal team.

Application fit: NVIDIA GB300, GB200, H200 accelerators; AMD EPYC SP5 and Intel Xeon CPUs; rack manifolds and CDU-connected loops. This page targets the AI-server-cooling application; component specs live on the linked product pages.

SUPPORTED PLATFORMS

Which GPU server platforms do we make cold plates for?

Four NVIDIA platforms are supplied as standard kits per their spec sheets; everything else is a custom GPU server cold plate quoted after a DFM review.

PlatformPart / referenceSupply basisDetails
NVIDIA GB3004 GPU + 2 CPU kit, TC-BZP-GB300-01AStandard (per spec sheet)GB300 cold plate specs
NVIDIA GB200TC-BZP-GB200-01A; 1,200 W + 1,200 W + 300 W (2× GPU + Grace CPU) at 2.5 L/minStandard (per spec sheet)GB200 cold plate
NVIDIA H200TC-BZP-H200-01AStandard (per spec sheet)H200 cold plate
NVIDIA H100T-HS202323Standard (per spec sheet)H100 cold plate
AMD EPYC SP5 / Intel XeonServer CPU cold platesCustomServer CPU cold plates
Other GPUs, ASICs, switches, opticsBuilt to your drawing and heat mapCustomCustom liquid cold plates

GB200 values from datasheet TC-BZP-GB200-01A. Any change to GPU/CPU count, envelope, or port layout turns a standard kit into a custom project.

STANDARD VS CUSTOM

When should you choose a standard kit and when a custom GPU server cold plate?

Choose a standard kit when your tray matches one of the four listed NVIDIA layouts; choose a custom GPU server cold plate when the layout, heat load, coolant, or interfaces differ.

If your project has…ChooseWhy
Your tray matches a listed platform layoutStandard kitSpec sheet already defines interfaces and test data; fastest path to samples
Different GPU/CPU count, envelope, or port positionsCustom cold plateChannel layout and ports are designed to your drawing
Heat load or coolant outside the spec-sheet envelopeCustom cold plateCFD review sizes channels to your flow and pressure-drop limit
New accelerator, ASIC, switch, or co-packaged opticsCustom cold plateNo standard kit exists; DFM review starts from your heat-source map
PROJECT FLOW

How does a custom GPU server cold plate project run?

A custom GPU server cold plate project runs in five steps, from RFQ to validated production, with US-side coordination through ToneCooling Texas LLC.

StepWhat happens
1. RFQSend drawings or STEP, heat load and heat-source map, coolant, flow, pressure-drop limit, quantity, and US delivery location. An engineer reviews every RFQ and replies by email with next steps.
2. NDA and DFM reviewA mutual NDA can be signed before drawing review. Engineers confirm envelope, ports, material, and joining route, and flag any changes that reduce risk or cost.
3. CFD and designFlow and thermal simulation checks channel layout against your flow rate and pressure-drop limit before samples are built.
4. SamplesCustom samples are available from a single piece. Sample and prototype lead time is typically 4–6 weeks, including design and simulation.
5. Validation and productionEvery unit is 100% helium leak-tested (acceptance criteria per project); thermal resistance, leak, and flatness test reports are available. Production lead time is confirmed at quotation for each project.

Related: cold plate RFQ checklist · NDA and IP protection · custom cold plate lead time · DDP shipping into the USA

MEASURED DATA

What performance data is published for GPU server cold plates?

Measured data is published for the standard kits. For the GB300 4G+2C kit, the GPU cold plate measured 0.0133 °C/W thermal resistance and 12.06 kPa pressure drop at 1.7 L/min and 1,066.94 W, and the CPU cold plate measured 0.0220 °C/W and 10.39 kPa at 0.7 L/min and 485.46 W (ToneCooling steady-state test with pure water, 2026-03-20).

Cold plateFlowHeat loadThermal resistancePressure drop
GB300 GPU cold plate1.7 L/min1,066.94 W0.0130–0.0133 °C/W12.06 kPa
GB300 CPU cold plate0.7 L/min485.46 W0.0220 °C/W10.39 kPa

Source: GB300 datasheet TC-DS-GB300-01A Rev. B. Full specs and the downloadable test summary are on the GB300 cold plate specs section. For custom designs, thermal resistance is validated per project by CFD and sample testing.

BUYER CHECKLIST

How do you choose a custom cold plate manufacturer for GPU servers?

Choose a custom cold plate manufacturer for GPU servers by checking eight things you can verify before a purchase order:

  1. Spec-sheet data: published flow, heat load, thermal resistance, and pressure drop with test conditions and date.
  2. Leak testing: 100% helium leak testing on every unit, with acceptance criteria agreed per project.
  3. Test reports: thermal resistance, leak, and flatness reports available for your samples.
  4. Own manufacturing: who actually makes the cold plate, and where.
  5. Quality system: ISO 9001 certification and automotive-grade process discipline (for example IATF 16949-aligned).
  6. Sample policy: whether samples are available from a single piece and how long prototypes take.
  7. US commercial support: a US entity for RFQs, NDA, and delivery terms such as DDP.
  8. IP protection: a mutual NDA before drawings are shared.

How ToneCooling answers each check for US buyers

CheckHow ToneCooling answers it for US buyers
Spec-sheet dataGB300 (4 GPU + 2 CPU), GB200, H200, and H100 kits are supplied according to their spec sheets; the GB300 cold plate datasheet summary can be downloaded without a form.
Leak testing100% helium leak testing; acceptance criteria are agreed per project.
Test reportsThermal resistance, leak, and flatness test reports are available.
Own manufacturingCold plates are made in our own manufacturing facility in Huizhou. Manifolds, quick disconnects, and hose sets are supplied by ToneCooling from China.
Quality systemISO 9001:2015 certified; IATF 16949-aligned quality system.
Sample policyCustom samples are available from a single piece. Sample and prototype lead time is typically 4–6 weeks including design and simulation.
US commercial supportToneCooling Texas LLC in Austin, TX handles RFQs, US-hours communication, and delivery terms such as DDP shipping to the USA.
IP protectionA mutual NDA can be signed before drawings are shared — see NDA and IP protection for cold plate RFQs.

See also how to qualify a cold plate supplier.

MANUFACTURING ROUTE

Process, quality, and manufacturing disclosure

Process optionsFSW, vacuum brazing, CAB, and TLP diffusion bonding in copper (C1100) and aluminum (6061); CFD flow/thermal validation; 100% helium leak testing.
QualityISO 9001:2015 certified; IATF 16949-aligned quality system; 100% helium leak testing; thermal resistance, leak, and flatness test reports available.
US support roleToneCooling Texas handles RFQ intake, US-hours communication, NDA, DFM follow-up, and US-side routing for AI-server cooling programs. The Texas entity is registered in Austin, TX, and does not manufacture.
Manufacturing disclosureManufacturing is performed by ToneCooling Technology Co., Ltd at the 30,000 m² facility in Huizhou, Guangdong, China (since 2004). ToneCooling Texas LLC is the North American RFQ and engineering-communication entity and does not manufacture.

Ready to discuss your liquid cooling project?

An engineer reviews every RFQ and replies by email with next steps. Send drawings, specs, or a project description.

FREQUENTLY ASKED

Common questions from US engineering & procurement teams

Do you support US AI server liquid cooling?

Yes. ToneCooling Texas coordinates US RFQs for direct-to-chip GPU and CPU cold plates, manifolds, and quick disconnects for AI server and data-center deployments.

Which platforms are supported?

NVIDIA GB300, GB200, H200, and AMD EPYC SP5 / Intel Xeon, with manifold and CDU-loop review.

What heat load can the assemblies handle?

Heat load is confirmed per drawing and platform under defined test conditions. For reference, the GB200 cold plate datasheet lists 1,200 W + 1,200 W + 300 W (2× GPU + Grace CPU) at 2.5 L/min.

Where are the cold plates made?

In our own manufacturing facility in Huizhou, Guangdong, China. Manifolds, quick disconnects, and hoses are supplied by ToneCooling from China. ToneCooling Texas LLC (Austin, TX) is the US RFQ and engineering entity and does not manufacture.

Who manufactures custom cold plates for GPU servers for US buyers?

ToneCooling makes custom GPU server cold plates in its own manufacturing facility in Huizhou, China, and ToneCooling Texas LLC in Austin, TX handles US RFQs, NDAs, and delivery terms. Standard kits cover NVIDIA GB300, GB200, H200, and H100; other layouts are custom.

What do you need to quote a custom GPU server cold plate?

Send drawings or a STEP model, heat load and heat-source map, coolant type and inlet temperature, flow rate and pressure-drop limit, envelope and port layout, quantity, and US delivery location. An engineer reviews every RFQ and replies by email with next steps.

Can we order a single GPU cold plate sample?

Yes. Custom samples are available from a single piece. Sample and prototype lead time is typically 4–6 weeks, including design and simulation; production lead time is confirmed at quotation for each project.

What GB300 cold plate test data is available?

The GB300 GPU cold plate measured 0.0133 °C/W and 12.06 kPa at 1.7 L/min and 1,066.94 W; the CPU cold plate measured 0.0220 °C/W and 10.39 kPa at 0.7 L/min (ToneCooling steady-state test with pure water, 2026-03-20).